AEG Moulded Case Circuit Breakers MC9 800-1600A
AEG Moulded Case Circuit Breakers MC9 800-1600A
The MC809, MC1259 and MC1609 breakers have respectively 800A, 1250A and 1600A rated current, in the same size. They can be equipped with thermomagnetic or electronic protection relay, type Line protection, Generator, Magnetic motor protection, isolator.
The electronic protection has three different versions: SMR1e for LT and ST channels, SMR1s with adjustable delay time, SMR1g with ground protection channel. The breakers are available as 3 or 4 poles version with neutral protection as 0%, 50%, 100% of the rated current.
The size and overall dimensions are the same for all breakers from 800A to 1600A.
- Thermal setting (In) (A)
- 320-1600
- Rated insulation voltage AC (Un)
- 1000
- Rated operational voltage Ue (Volts) AC/DC
- 690/500
- Ultimate breaking capacity Icu @400/415V AC(kA)
- S=50, H=80, X=100,
- Category of use
- B
- Non automatic breaker (Switch) (A)
- 800,1000,1250,1600
- Weights
- 800A (3P=12,2kg; 4P=15,1kg); 1250,1600A(3P=18kg, 4P=23,4kg)
- Dimensions (w x h x d) mm
- 3P=210 x 320 x 160; 4P=280 x 320 x 160;
- Endurance CO operations Mechanical/Electrical at In
- 800A= 10000/4000; 1250A=10000/3000; 1600A=10000/2000
- Mounting
- Fixed, Draw out
- Approval / Marking
- EN60947-2